电动防火阀 排烟防火阀 正压送风口(加压送风口) 排烟口(多叶排烟口)安装方法和注意事项


Installation method and precautions of positive pressure air supply port (pressurized air supply port) smoke exhaust port (multi-leaf smoke exhaust port) of electric fire valve smoke exhaust and fire valve

安装阀体之前应先检查阀门外形及操作机构是否完好,动作是否灵活,确认阀门各方面都正常之后,再进行安装。


Before installing the valve body, check the shape of the valve and the operation mechanism is intact and the action is flexible. After confirming that all aspects of the valve are normal, install the valve.

2

Two

安装排烟阀、排烟防火阀时,阀体的一侧应预留出位置,一般应不小于350mm的净空间,便于定期的动作试验和检查。


When installing smoke exhaust valve and smoke exhaust fire prevention valve, one side of the valve body should be reserved, and the net space should be no less than 350 mm in general, so as to facilitate regular operation test and inspection.

3

Three

2-161101135457.jpg

阀门在安装之前或在安装以后的使用中,应定期进行开启动作试验,建议每半年至一年进行一次。动作试验包括使用电讯号使阀门开启或手动开启,阀门动作后应有电讯号输出。

Valves should be opened regularly before or after installation. It is recommended that the valve be opened every six months to one year. Action test includes the use of telecommunication signals to open or manually open the valve. After the valve is operated, there should be an output of telecommunication signals.